14 AWG stranded (7x22) TC conductors. conductors cabled. plenum. FEP insulation. Beldfoil (100% coverage) + TC braid shield (85% coverage). FEP jacket.
Specifications
Temp Range, Operating | -70ºC To +200ºC |
---|---|
Temp Rating, UL | 200ºC |
Capacitance | 52.000 |
Capacitance (Metric) | 170.612 |
Current, Max. Recomm. | 18 Amps per conductor @ 25ºC |
Inductance | .160 |
Inductance (Metric) | 0.52496 |
Voltage, Max. Operating | 300 V RMS (UL AWM Style 1424) |
SKU | B-83752-500 |
Manufacturer | Belden |
CEC/C(UL) Specification | CMP |
RoHS | Yes |
EU CE Mark | Yes |
NEC/(UL) Specification | FPLP. CMP |
Mfr. Part No | 83752 002500 |
Plenum | Yes |
Flame Test - UL Flame Test | NFPA 262 |
Weight | 0.0630 |
Color | RED |
Type | Non-Paired |
Conductor Size (AWG) | 14 |
Conductor Material | TC - Tinned Copper |
Number of Conductors | 2 |
Conductor Stranding | 7x22 |
Insulation Material | FEP - Fluorinated Ethylene Propylene |
Insulation Wall Thickness | .016 |
Insulation Wall Thickness (Metric) | 0.4064 |
Overall Nominal Diameter | .267 |
Outer Jacket Wall Thickness | .015 |
Outer Jacket Material | FEP - Fluorinated Ethylene Propylene |
Outer Shield Coverage | 100^85 |
Outer Shield Material | Aluminum Foil-Polyester Tape^TC - Tinned Copper |
Outer Shield Type | Tape^Braid |
Amount | 500 ft |
Overall Cabling - Overall Nominal Diameter (Metric) | 6.7818 |
Outer Jacket - Nom. Wall Thickness (Metric) | 0.381 |